Description
The underlying feedback mechanism of Rockwell Automation's FactoryTalk System Services that transfers the FactoryTalk Policy Manager rules to relevant devices on the network does not verify that the origin of the communication is from a legitimate local client device. This may allow a threat actor to craft a malicious website that, when visited, will send a malicious script that can connect to the local WebSocket endpoint and wait for events as if it was a valid client device. If successfully exploited, this would allow a threat actor to receive information including whether FactoryTalk Policy Manager is installed and potentially the entire security policy.
References
Note: References are provided for the convenience of the reader to help distinguish between vulnerabilities. The list is not intended to be complete.
Assigning CNA
Rockwell Automation
Date Record Created
20230510 Disclaimer: The record creation date may reflect when the CVE ID was allocated or reserved, and does not necessarily indicate when this vulnerability was discovered, shared with the affected vendor, publicly disclosed, or updated in CVE.
Phase (Legacy)
Assigned (20230510)
Votes (Legacy)
Comments (Legacy)
Proposed (Legacy)
N/A
This is an record on the CVE List, which provides common identifiers for publicly known cybersecurity vulnerabilities.