CVE-ID | ||
---|---|---|
CVE-2022-4608 |
• CVSS Severity Rating • Fix Information • Vulnerable Software Versions • SCAP Mappings • CPE Information
|
|
Description | ||
A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is expired an RTU500 initiated update of session parameters causes an unexpected restart due to a stack overflow. | ||
References | ||
Note: References are provided for the convenience of the reader to help distinguish between vulnerabilities. The list is not intended to be complete. | ||
Assigning CNA | ||
Hitachi Energy | ||
Date Record Created | ||
20221219 | Disclaimer: The record creation date may reflect when the CVE ID was allocated or reserved, and does not necessarily indicate when this vulnerability was discovered, shared with the affected vendor, publicly disclosed, or updated in CVE. | |
Phase (Legacy) | ||
Assigned (20221219) | ||
Votes (Legacy) | ||
Comments (Legacy) | ||
Proposed (Legacy) | ||
N/A | ||
This is an record on the CVE List, which provides common identifiers for publicly known cybersecurity vulnerabilities. | ||
You can also search by reference using the CVE Reference Maps.
|
||
For More Information: CVE Request Web Form (select "Other" from dropdown) |