|
|
CVE-ID | ||
---|---|---|
CVE-2022-33175 |
• CVSS Severity Rating • Fix Information • Vulnerable Software Versions • SCAP Mappings • CPE Information
|
|
Description | ||
Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 have an insecure permissions setting on the user.token field that is accessible to everyone through the /cgi/get_param.cgi HTTP API. This leads to disclosing active session ids of currently logged-in administrators. The session id can then be reused to act as the administrator, allowing reading of the cleartext password, or reconfiguring the device. | ||
References | ||
Note: References are provided for the convenience of the reader to help distinguish between vulnerabilities. The list is not intended to be complete. | ||
Assigning CNA | ||
MITRE Corporation | ||
Date Record Created | ||
20220613 | Disclaimer: The record creation date may reflect when the CVE ID was allocated or reserved, and does not necessarily indicate when this vulnerability was discovered, shared with the affected vendor, publicly disclosed, or updated in CVE. | |
Phase (Legacy) | ||
Assigned (20220613) | ||
Votes (Legacy) | ||
Comments (Legacy) | ||
Proposed (Legacy) | ||
N/A | ||
This is an record on the CVE List, which provides common identifiers for publicly known cybersecurity vulnerabilities. | ||
You can also search by reference using the CVE Reference Maps.
|
||
For More Information: CVE Request Web Form (select "Other" from dropdown) |