Description
Honeywell Experion LX through 2022-05-06 has Missing Authentication for a Critical Function. According to FSCT-2022-0055, there is a Honeywell Experion LX Control Data Access (CDA) EpicMo protocol with unauthenticated functionality issue. The affected components are characterized as: Honeywell Control Data Access (CDA) EpicMo (55565/TCP). The potential impact is: Firmware manipulation, Denial of service. The Honeywell Experion LX Distributed Control System (DCS) utilizes the Control Data Access (CDA) EpicMo protocol (55565/TCP) for device diagnostics and maintenance purposes. This protocol does not have any authentication features, allowing any attacker capable of communicating with the ports in question to invoke (a subset of) desired functionality. There is no authentication functionality on the protocol in question. An attacker capable of invoking the protocols' functionalities could issue firmware download commands potentially allowing for firmware manipulation and reboot devices causing denial of service.
References
Note: References are provided for the convenience of the reader to help distinguish between vulnerabilities. The list is not intended to be complete.
Assigning CNA
MITRE Corporation
Date Record Created
20220506 Disclaimer: The record creation date may reflect when the CVE ID was allocated or reserved, and does not necessarily indicate when this vulnerability was discovered, shared with the affected vendor, publicly disclosed, or updated in CVE.
Phase (Legacy)
Assigned (20220506)
Votes (Legacy)
Comments (Legacy)
Proposed (Legacy)
N/A
This is an record on the CVE List, which provides common identifiers for publicly known cybersecurity vulnerabilities.