CVE-ID |
CVE-2019-19281
|
• CVSS Severity Rating • Fix Information • Vulnerable Software Versions • SCAP Mappings • CPE Information
|
Description |
A vulnerability has been identified in SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions >= V2.5 and < V20.8), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.5 and < V2.8), SIMATIC S7-1500 Software Controller (All versions >= V2.5 and < V20.8). Affected devices contain a vulnerability that allows an unauthenticated attacker to trigger a Denial-of-Service condition. The vulnerability can be triggered if specially crafted UDP packets are sent to the device. The security vulnerability could be exploited by an attacker with network access to the affected systems. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise the device availability.
|
References |
Note: References are provided for the convenience of the reader to help distinguish between vulnerabilities. The list is not intended to be complete.
|
|
Assigning CNA |
Siemens |
Date Record Created |
20191126 |
Disclaimer: The record creation date may reflect when
the CVE ID was allocated or reserved, and does not
necessarily indicate when this vulnerability was
discovered, shared with the affected vendor, publicly
disclosed, or updated in CVE.
|
Phase (Legacy) |
Assigned (20191126) |
Votes (Legacy) |
|
Comments (Legacy) |
|
Proposed (Legacy) |
N/A |
This is an record on the CVE List, which provides common identifiers for publicly known cybersecurity vulnerabilities. |
|
For More Information: CVE Request Web Form (select "Other" from dropdown)
|