• Severity Rating • Fix Information • Vulnerable Software Versions • SCAP Mappings
Core Server HMI Service (Coreservice.exe) in Scadatec Limited Procyon SCADA 1.06, and other versions before 1.14, allows remote attackers to cause a denial of service (crash) and possibly execute arbitrary code via a long password to the Telnet (TCP/23) port, which triggers an out-of-bounds read or write, leading to a stack-based buffer overflow.
Note: References are provided for the convenience of the reader to help distinguish between vulnerabilities. The list is not intended to be complete.
Date Entry Created
20110829 Disclaimer: The entry creation date may reflect when the CVE-ID was allocated or reserved, and does not necessarily indicate when this vulnerability was discovered, shared with the affected vendor, publicly disclosed, or updated in CVE.
Phase (Legacy)
Assigned (20110829)
Votes (Legacy)
Comments (Legacy)
Proposed (Legacy)
This is an entry on the CVE list, which standardizes names for security problems.