CVE-ID

CVE-2023-2071

• CVSS Severity Rating • Fix Information • Vulnerable Software Versions • SCAP Mappings • CPE Information
Description
Rockwell Automation FactoryTalk View Machine Edition on the PanelView Plus, improperly verifies user’s input, which allows unauthenticated attacker to achieve remote code executed via crafted malicious packets. The device has the functionality, through a CIP class, to execute exported functions from libraries. There is a routine that restricts it to execute specific functions from two dynamic link library files. By using a CIP class, an attacker can upload a self-made library to the device which allows the attacker to bypass the security check and execute any code written in the function.
References
Note: References are provided for the convenience of the reader to help distinguish between vulnerabilities. The list is not intended to be complete.
Assigning CNA
Rockwell Automation
Date Record Created
20230414 Disclaimer: The record creation date may reflect when the CVE ID was allocated or reserved, and does not necessarily indicate when this vulnerability was discovered, shared with the affected vendor, publicly disclosed, or updated in CVE.
Phase (Legacy)
Assigned (20230414)
Votes (Legacy)
Comments (Legacy)
Proposed (Legacy)
N/A
This is an record on the CVE List, which provides common identifiers for publicly known cybersecurity vulnerabilities.