CVE-ID |
CVE-2020-28397
|
• CVSS Severity Rating • Fix Information • Vulnerable Software Versions • SCAP Mappings • CPE Information
|
Description |
A vulnerability has been identified in SIMATIC Drive Controller family (All versions < V2.9.2), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V21.9), SIMATIC S7 PLCSIM Advanced (All versions > V2 < V4), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (Version V4.4), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions > V2.5 < V2.9.2), SIMATIC S7-1500 Software Controller (All versions > V2.5 < V21.9), TIM 1531 IRC (incl. SIPLUS NET variants) (Version V2.1). Due to an incorrect authorization check in the affected component, an attacker could extract information about access protected PLC program variables over port 102/tcp from an affected device when reading multiple attributes at once.
|
References |
Note: References are provided for the convenience of the reader to help distinguish between vulnerabilities. The list is not intended to be complete.
|
|
Assigning CNA |
Siemens |
Date Record Created |
20201110 |
Disclaimer: The record creation date may reflect when
the CVE ID was allocated or reserved, and does not
necessarily indicate when this vulnerability was
discovered, shared with the affected vendor, publicly
disclosed, or updated in CVE.
|
Phase (Legacy) |
Assigned (20201110) |
Votes (Legacy) |
|
Comments (Legacy) |
|
Proposed (Legacy) |
N/A |
This is an record on the CVE List, which provides common identifiers for publicly known cybersecurity vulnerabilities. |
|
For More Information: CVE Request Web Form (select "Other" from dropdown)
|